PACIFIC RESEARCHPET-820REMOTE MONITORING AND CONTROLUSER MANUALThis manual contains information proprietary to Pacific Research and is provided for th
Pacific Research PET-820 User ManualPage 92.2.1 ANALOG INPUT OPTION START UP PROCEDUREThe following is a start up procedure for the PET-820's Ana
Pacific Research PET-820 User ManualPage 102.4 OPERATE PROCEDURERather than using examples of all commands, you will only ARM the PET-820. This is do
Pacific Research PET-820 User ManualPage 11OPERATING INSTRUCTIONS3.0 OPERATINGThe operating commands are the principle means for the user to control t
Pacific Research PET-820 User ManualPage 123.2.3 READY INDICATORThis indicator is used to identify the condition of the loop circuit inputs. Use the
Pacific Research PET-820 User ManualPage 133.3 OPERATING COMMAND FORMATAll operating commands contain four parts. The first part [Command Code] defin
Pacific Research PET-820 User ManualPage 143.7 VALID DATA TYPESMost all operating command codes only require values of zero (0) through 9 or Zero (0)
Pacific Research PET-820 User ManualPage 153.9.2 ARM/DISARMThis command is used to arm and disarm the PET-820. Once an alarm occurs and the PET-820 ha
Pacific Research PET-820 User ManualPage 163.9.5 LOOP CIRCUIT ON/OFFThis command may be used to turn ON or OFF any of the 8 loop circuits without effe
Pacific Research PET-820 User ManualPage 173.9.10 RELAY AND DIGITAL OUTPUT CONTROLThis command allows the user to directly control the operation of th
Pacific Research PET-820 User ManualPage 183.9.14 READ ANALOG LOW (MINIMUM) VALUEThis command reads the minimum analog voltage which occurred since th
Pacific Research PET-820 User ManualPage 1TABLE OF CONTENTSSYSTEM OVERVIEW ...
Pacific Research PET-820 User ManualPage 19PROGRAMMING INSTRUCTIONS4.0 PROGRAMMINGProgramming is the principle means for the user to configure with a
Pacific Research PET-820 User ManualPage 204.3.1 DATA TYPES USEDSome data values have maximum values and if you exceed these values the command will b
Pacific Research PET-820 User ManualPage 214.5.2 CHANGE PROGRAM AUTHORIZATION CODEChanging the PROGRAM AUTHORIZATION CODE consist of the command code
Pacific Research PET-820 User ManualPage 224.5.6 ARM DELAYIn applications where the PET-820 is used to monitor exit or entrance doors the ARM DELAY ma
Pacific Research PET-820 User ManualPage 234.5.10 PASSWORD ATTEMPT ERRORSWhen communication has been established, a counter will keep track of the num
Pacific Research PET-820 User ManualPage 244.5.12 CHANGE TELEPHONE NUMBERThe PET-820 is capable of dialing a 32 digit telephone number. This number c
Pacific Research PET-820 User ManualPage 254.5.14 CHANGE SPEECH MESSAGE BUFFER DATAThis command is used to alter the data in the pre-selected speech m
Pacific Research PET-820 User ManualPage 264.5.15 SELECT SIGN ON MESSAGEThe sign on message is the message that is sent when the user calls the PET-82
Pacific Research PET-820 User ManualPage 274.5.18 ALARM MESSAGE REPEATThis function allows you to define the number of times the alarm message is repe
Pacific Research PET-820 User ManualPage 284.5.21 CHANGE LOOP CONFIGURATION, SELECT ALARM RELAY OUTPUTEach of the loop circuits can be configured in a
Pacific Research PET-820 User ManualPage 24.0 PROGRAMMING ...
Pacific Research PET-820 User ManualPage 294.5.23 CHANGE LOOP CONFIGURATION, SELECT RESPONSE TIMEEach loop circuit can be programmed to use one of two
Pacific Research PET-820 User ManualPage 304.5.26 EIGHT NUMBER TELEPHONE LOGWhen the optional RAM/RTC is installed, the PET-820 is capable of dialing
Pacific Research PET-820 User ManualPage 314.5.28 SET DAY OF WEEK, RTC OPTIONIf your PET-820 has included the Real Time Clock option, the day of week
Pacific Research PET-820 User ManualPage 324.5.32 LOCAL ARM/DISARM CONTROLThis feature allows the user to add a local ARM/DISARM switch for arm and di
Pacific Research PET-820 User ManualPage 334.5.36 SELECT DTMF/DIAL PULSE MODEThis feature allows the user to select the initial mode in which a teleph
Pacific Research PET-820 User ManualPage 344.5.39 SERIAL PORT BAUD RATEIf your PET-820 has included a serial port, you may use this command to select
Pacific Research PET-820 User ManualPage 354.5.46 SYSTEM EEPROM INITIALIZATIONThis command will re-initialize all of the systems characteristics to th
Pacific Research PET-820 User ManualPage 364.6.1 RESET ANALOG HIGH AND LOW VALUESThis command is used to reset the analog values in the high and low (
Pacific Research PET-820 User ManualPage 374.6.3 SET ANALOG INPUT INTEGRATE RATEThe integrate rate is used to filter each of the analog inputs so that
Pacific Research PET-820 User ManualPage 384.6.6 SELECT TELEPHONE NUMBER ACCESS FOR EACH ANALOG INPUT ALARMOnce an analog input alarm condition has be
Pacific Research PET-820 User ManualPage 34.6.1 Reset analog high and low values4.6.2 Set analog high and low alarm setpoints4.6.3 Set analog input in
Pacific Research PET-820 User ManualPage 394.6.9 SELECT ADC MODE, SINGLE / DIFFERENTIAL ENDED INPUTThis feature allows the analog inputs to be used in
Pacific Research PET-820 User ManualPage 404.6.12.1 SET OFFSET VALUESThis command may be used to add or subtract a value or voltage from the analog to
Pacific Research PET-820 User ManualPage 41The following list are items to consider while you are setting up values for the purpose of scaling.1. Use
Pacific Research PET-820 User ManualPage 424.6.12.4 SET DECIMAL POINT ROUND OFFThe decimal point round off is used to define the number of digits righ
Pacific Research PET-820 User ManualPage 43COMMUNICATION5.0 COMMUNICATIONThe PET-820 is equipped with the latest technology in digital speech synthesi
Pacific Research PET-820 User ManualPage 445.1.4 DIAL AND COMMUNICATION DELAYSThe PET-820 allows for delays before going OFF HOOK, dialing a telephone
Pacific Research PET-820 User ManualPage 455.3.1 SERIAL COMMAND MODEThe serial command mode operates much in the same manner as the Touch-Tone command
Pacific Research PET-820 User ManualPage 465.5.1 TELEPHONE COMPANY REQUIREMENTSAll connections to the telephone network must be made through standard
Pacific Research PET-820 User ManualPage 47EQUIPMENT INSTALLATION6.0 INSTALLATIONThe PET-820 was designed for wall mount installation. The enclosure
Pacific Research PET-820 User ManualPage 486.3.2 TO MOUNT ON CONCRETE OR MORTAR WALLS1. Place the template (included in "Appendix-D") on the
Pacific Research PET-820 User ManualPage 49.0 GLOSSARY AND WARRANTY ... PAGE
Pacific Research PET-820 User ManualPage 496.4.1 ANALOG INPUT CONNECTIONSThe following section outlines connections that are importation to the analog
Pacific Research PET-820 User ManualPage 506.7 CALIBRATION, ANALOG INPUT OPTIONCalibration adjustments to the analog input option are done via the two
Pacific Research PET-820 User ManualPage 51FIGURE - 6.1
Pacific Research PET-820 User ManualPage 52FIGURE - 6.2
Pacific Research PET-820 User ManualPage 53FIGURE - 6.3FIGURE - 6.4
Pacific Research PET-820 User ManualPage 54TROUBLESHOOTING7.0 STANDARD TROUBLESHOOTINGThis section provides procedures to solve some common problems t
Pacific Research PET-820 User ManualPage 55GLOSSARY AND WARRANTY REPAIR8.0 GLOSSARYADC: Analog to Digital Converter, this is a device or circuit tha
Pacific Research PET-820 User ManualPage 56PROGRAM AUTHORIZATION CODE: A programmable code that allows access to programming or changingcharacterist
Pacific Research PET-820 User ManualPage 57LIMITED WARRANTYPACIFIC RESEARCH will repair this product with new or rebuilt parts free of charge in the U
Pacific Research PET-820 User ManualPage 58OPERATE COMMAND TABLECommandCodeCommand Description CommandSyntax60 PasswordSee programming table for defau
Pacific Research PET-820 User ManualPage 5INTRODUCTIONThe PET-820 (Personal Electronic Technician) represents the latest technological advances in the
Pacific Research PET-820 User ManualPage 59PROGRAMMING TABLECommandCodeProgramming Command Description CommandSyntaxFactorySettingNewSetting10 Set loo
Pacific Research PET-820 User ManualPage 60PROGRAMMING TABLECommandCodeProgramming Command Description CommandSyntaxFactorySettingNewSetting30 LOOP CO
Pacific Research PET-820 User ManualPage 61PROGRAMMING TABLECommandCodeProgramming Command Description CommandSyntaxFactorySettingNewSetting37 Set tel
Pacific Research PET-820 User ManualPage 62PROGRAMMING TABLECommandCodeProgramming Command Description CommandSyntaxFactorySettingNewSetting60 Reserve
Pacific Research PET-820 User ManualPage 63ADC OPTION PROGRAMMING TABLECommandCodeProgramming CommandDescriptionNew Analog settings1 2 3
Pacific Research PET-820 User ManualPage 64SPEECH LIBRARYIf your application requires words that are not listed in this manual, additional words and c
Pacific Research PET-820 User ManualPage 65LOW WORD GROUP LOW WORD GROUP LOW WORD GROUPWORD ADDRESS WORD ADDRESS WORD ADDRESSR 064 DIRECTION 113 LEVEL
Pacific Research PET-820 User ManualPage 66LOW WORD GROUP HIGH WORD GROUPFEMALE VOICEHIGH WORD GROUPWORD ADDRESS WORD ADDRESS WORD ADDRESSRED 211 THE
Pacific Research PET-820 User ManualPage 67HIGH WORD GROUP HIGH WORD GROUP HIGH WORD GROUPWORD ADDRESS WORD ADDRESS WORD ADDRESSGOOD-BYE 099 SS (SOUND
Pacific Research PET-820 User ManualPage 68SPEECH MESSAGE BUFFER PROGRAMMING TABLEBUFFERADDRESS SPEECH WORD DATA00 WORD 00 WORD 01 WORD 02 WORD 03 WOR
Pacific Research PET-820 User ManualPage 6SYSTEM DESCRIPTION1.0 SYSTEM OVERVIEWThe PET-820 system is shipped from the factory ready for use. It comes
Pacific Research PET-820 User ManualPage 69SPEECH MESSAGE BUFFER PROGRAMMING TABLEBUFFERADDRESS SPEECH WORD DATA06 WORD 00 WORD 01 WORD 02 WORD 03 WOR
Pacific Research PET-820 User ManualPage 70SPEECH MESSAGE BUFFER PROGRAMMING TABLEBUFFERADDRESS SPEECH WORD DATA12 WORD 00 WORD 01 WORD 02 WORD 03 WOR
Pacific Research PET-820 User ManualPage 71EEPROM PROGRAMMING DATA TABLEADDRESS DEFAULT DATA DESCRIPTION000 001 LOOP RESPONSE 1, 40 mS001 025 LOOP RES
Pacific Research PET-820 User ManualPage 72SYSTEM CONFIGURATION BYTE 1BIT NO. BYTEADDRESSDEFAULT DESCRIPTION765432101 0 NEW EEPROM FLAG765432102 2 LOC
Pacific Research PET-820 User ManualPage 73LOOP DEFINITION, LOW BYTEBIT NO. BYTEADDERDEFAULT DESCRIPTION765432101 0 LOOP TYPE B0, 0 = DISABLE, 1 = N.C
Pacific Research PET-820 User ManualPage 71.5 ANALOG OPTIONThe analog option is used to monitor analog voltages and initiate an alarm if a voltage goe
Pacific Research PET-820 User ManualPage 8GETTING STARTED2.0 BENCH TESTINGThe following paragraphs provide a method for becoming familiar with the PET